DC Output Power<\/strong>
\n7 Adc at 63 Vdc maximum continuous with a 240 Vac input.
\nExciter Field DC Resistance<\/strong>
\n9.0 ohms minimum.
\nAC Power Input<\/strong>
\n170 to 305 Vac, single-phase, 50\/60 Hz.
\nBurden: 900 VA maximum at 240 Vac power.
\nAC Sensing Voltage<\/strong>
\n170 to 264 Vac, single-phase, 50\/60 Hz.
\nBurden: 5 VA.
\nVoltage Adjust Range<\/strong>
\n170 to 264 Vac using the internal voltage adjust. The
\nexternal voltage adjust provides a \u00b110% adjustment of the
\nnominal value determined by the internal voltage adjust.
\nRegulation<\/strong> Accuracy<\/strong>
\n\u00b10.25%
\nVoltage Drift<\/strong>
\n<\u00b11% voltage variation for a 50\u00b0C (122\u00b0F) change.
\nResponse Time<\/strong>
\n<16 ms
\nFrequency Compensation<\/strong>
\nRefer to Figure 1.
\nVoltage Buildup<\/strong>
\nInternal provisions for automatic buildup from generator
\nresidual voltage as low as 6 Vac at 25 Hz.
\nPower Dissipation<\/strong>
\n35 W maximum
\nParalleling Provisions<\/strong>
\nCT input for customer supplied 5 A nominal CT. Adjustable
\ndroop from 0 to 6% with 5 A input at 0.8 power factor. CT
\ninput burden is 2.5 VA.<\/p>\ndatasheet<\/span><\/a>\n","protected":false},"excerpt":{"rendered":"